Capability & Infrastructure

Since after the resolution passed by government for doing IS-1180 mandatory for the distribution transformer from JANUARY 2017 onwards, we have undergone large RESEARCH & DEVELOPMENT for achieving the goal of making BIS approved transformer up to and including 2500 KVA distribution transformer of all level of efficiency wiz:- LEVEL-1, LEVEL-2, and LEVEL-3.

Now we proudly say that we are a successful manufacturer of BIS approved distribution transformer on the basis of our HAPPY CUSTOMERS using our HIGHLY EFFICIENT BIS APPROVED:- IS 1180 transformer uninterruptedly.

Maximum Total Losses Upto 11 kV Class Transformers

(Clauses 7.8.1.1, 7.8.1.2, 7.8.1.3 & 7.8.2)

Sr. No. KVA Impedance % Maximum Total Loss (W) @ 75˚ Celsius
LEVEL 1 LEVEL 2 LEVEL 3
50% 100% 50% 100% 50% 100%
1 250 4.5 1050 3150 980 2930 920 2700
2 315 4.5 1100 3275 1025 3100 955 2750
3 400 4.5 1300 3875 1225 3450 1150 3330
4 500 4.5 1600 4750 1510 4300 1430 4100
5 630 4.5 2000 5855 1860 5300 1745 4850
6 800 5.0 2459 7300 2287 6402 2147 5837
7 1000 5.0 3000 9000 2790 7700 2620 7000
8 1250 5.0 3600 10750 3300 9200 3220 8400
9 1600 6.25 4500 13500 4200 11800 3970 11300
10 2000 6.25 5400 17000 5050 15000 4790 14100
11 2500 6.25 6500 20000 6150 18500 5900 17500