Since after the resolution passed by government for doing IS-1180 mandatory for the distribution transformer from JANUARY 2017 onwards, we have undergone large RESEARCH & DEVELOPMENT for achieving the goal of making BIS approved transformer up to and including 2500 KVA distribution transformer of all level of efficiency wiz:- LEVEL-1, LEVEL-2, and LEVEL-3.
Now we proudly say that we are a successful manufacturer of BIS approved distribution transformer on the basis of our HAPPY CUSTOMERS using our HIGHLY EFFICIENT BIS APPROVED:- IS 1180 transformer uninterruptedly.
Maximum Total Losses Upto 11 kV Class Transformers
(Clauses 7.8.1.1, 7.8.1.2, 7.8.1.3 & 7.8.2)
Sr. No. | KVA | Impedance % | Maximum Total Loss (W) @ 75˚ Celsius | |||||
LEVEL 2 | LEVEL 3 | |||||||
50% | 100% | 50% | 100% | |||||
1 | 250 | 4.5 | 980 | 2930 | 920 | 2700 | ||
2 | 315 | 4.5 | 1025 | 3100 | 955 | 2750 | ||
3 | 400 | 4.5 | 1225 | 3450 | 1150 | 3330 | ||
4 | 500 | 4.5 | 1510 | 4300 | 1430 | 4100 | ||
5 | 630 | 4.5 | 1860 | 5300 | 1745 | 4850 | ||
6 | 800 | 5.0 | 2287 | 6402 | 2147 | 5837 | ||
7 | 1000 | 5.0 | 2790 | 7700 | 2620 | 7000 | ||
8 | 1250 | 5.0 | 3300 | 9200 | 3220 | 8400 | ||
9 | 1600 | 6.25 | 4200 | 11800 | 3970 | 11300 | ||
10 | 2000 | 6.25 | 5050 | 15000 | 4790 | 14100 | ||
11 | 2500 | 6.25 | 6150 | 18500 | 5900 | 17500 |